Toll Free: 800-535-3569Tel: 262-639-6770DDFXDDoppler Ultrasonic Flow MeterFORM # 06-DPP-UM-00147RUN
10 06-DPP-UM-00147 02/12USER SAFETYThe DFX employs modular construction and provides electrical safety for the operator. The enclosure is constructe
06-DPP-UM-00147 02/12 11PRODUCT MATRIXDDFXD DIGITAL DOPPLER ULTRASONIC FLOW TRANSMITTERDDFXD 2 - A - N NPower SupplyTransmitter Type2) Rate and Tot
12 06-DPP-UM-00147 02/12DP7 INSERTION DOPPLER PROBE*Cannot be used with hot tap assemblyConduit Length000) 0’ (0m)020) 20’ (6m)050) 50’ (15m)100) 10
06-DPP-UM-00147 02/12 13PART 2 TRANSDUCER INSTALLATIONUNPACKINGAfter unpacking, it is recommended to save the shipping carton and packing materials
14 06-DPP-UM-00147 02/12Select a transducer mounting location with adequate straight runs of pipe, both upstream and down-stream, to achieve stable
06-DPP-UM-00147 02/12 15PIPE PREPARATIONBefore the transducer heads are mounted to the pipe surface, an area slightly larger than the at surface of
16 06-DPP-UM-00147 02/12FLOWTop Viewof PipeFIGURE 2.3 TRANSDUCER PLACEMENTPROCEDURE:1) Large pipe installations utilize stainless steel straps to
06-DPP-UM-00147 02/12 174) Spread an even layer of coupling compound, approximately ⁄” (3 mm) thick, to the at face of the two transducers.5) Pla
18 06-DPP-UM-00147 02/12If the Bronze Hot Tap Kit (p.n. D030-1006-001) or Stainless Steel Hot Tap Kit (p.n. D030-1006-002) accessory kits were order
06-DPP-UM-00147 02/12 19PROBE INSERTIONBefore inserting the DP7 probe into the piping system, it is necessary to calculate the probe insertion depth
20 06-DPP-UM-00147 02/12NOTE: For some low pressure/low temperature applications [less than 30 PSI (2.1 Bar) and less than 100 °F (38 °C)], the prob
06-DPP-UM-00147 02/12 21Flow DirectionArrowFIGURE 2.7 FLOW DIRECTION ARROWPROBE CABLESBefore inserting the probe into the pipe, the sensor cables
22 06-DPP-UM-00147 02/12CAUTION: Do not run the drive nuts o the rods until the isolation valve is fully closed.2) After the probe is retracted pas
06-DPP-UM-00147 02/12 23PART 3 TRANSMITTER INSTALLATIONUNPACKINGAfter unpacking, it is recommended to save the shipping carton and packing materia
24 06-DPP-UM-00147 02/125.75"(146.1)3.93"(99.8)4.25"(108.0)7.00"(177.8)PowerConnectionTransducerConnectionInput/OutputConnection
06-DPP-UM-00147 02/12 25TRANSDUCER WIRING CONNECTIONSTo access terminal strips for electronic connectors, loosen the two screws in the enclosure door
26 06-DPP-UM-00147 02/12+C3JP2J3J4J2JP1JP324131346791012VPP12-800CLASS BR®VDELock NutGroundingWireFIGURE 3.3 TRANSDUCER CONNECTIONSPOWER SUPPLY WI
06-DPP-UM-00147 02/12 27MODULE #2MODULE #1JP1/JP2Connections115/230VACJP2JP1JP3J4J3J29-28 VDC9-28 VDC2143214321432143212121212121Fuse (5x20mm)AC: 0.
28 06-DPP-UM-00147 02/12AC POWER SUPPLY CONNECTIONSDANGER: Line voltages may be present within the enclosure. There is a risk of shock, sparks and d
06-DPP-UM-00147 02/12 29DC POWER SUPPLY CONNECTIONSThe DFX may be operated from a 12-28 VDC source, as long as the source is capable of supplying 7
06-DPP-UM-00147 02/12 3TABLE OF CONTENTSSYMBOL EXPLANATIONS ...
30 06-DPP-UM-00147 02/12MULTIPLE METER INSTALLATIONSThe DFX ow meter contains a provision for synchronizing multiple DFX ow meters together. Synch
06-DPP-UM-00147 02/12 31MODULE #2MODULE #1JP1/JP2Connections115/230VACJP2JP1JP3J4J3J29-28 VDC9-28 VDC2143214321432143212121212121Fuse (5x20mm)AC: 0.2
32 06-DPP-UM-00147 02/12+C3JP2J3J4J2JP1JP324131346791012VPP12-800CLASS BR®VDEMODULE #2MODULE #1JP1/JP2Connections115/230VACJP2JP1JP3J4J3J29-28 VDC9-
06-DPP-UM-00147 02/12 33INTERNAL POWER CONFIGURATIONEnsure that jumpers are in place at JP1 and JP2 on the module – reference Figure 3.10B. In this
34 06-DPP-UM-00147 02/12OUT (-)IN (+)I/O: 4-20 mAP.N. D020-1045-100ISO-MODJP2JP1INT PWR EXT PWRRTU/PLCMONITORRemoveJumpers4-20 mA IN (+)4-20 mA OUT (
06-DPP-UM-00147 02/12 35b NOb CMb NCa NOa CMa NCI/O: RELAYP.N. D020-1045-102ISO-MODPOWERRELAYPOWERSOURCEFIGURE 3.11B EXTERNAL RELAY CONNECTIONSRAT
36 06-DPP-UM-00147 02/120500 mVp-p0+VRTU/PLCMONITORTURBINE INTURBINE INRTU/PLCMONITORPULSE IN+V EXT SENSORGND0TIME+VR500 mVppTURBINE - BTURBINE - AIN
06-DPP-UM-00147 02/12 37PART 4 INSTRUMENT PROGRAMMINGGENERALThe DFX is congured through the keypad interface. All entries are saved in non-volati
38 06-DPP-UM-00147 02/12NUMERIC VALUE ENTRY PROCEDURENOTE: If you are already in PROGRAM mode and the selection to be viewed or changed is already d
06-DPP-UM-00147 02/12 39PIPE INSIDE DIAMETER PIPE ID -- Pipe Inside Diameter Entry (Value) ENGLSH (Inches) METRIC (Millimeters)Enter the pipe
4 06-DPP-UM-00147 02/12APPENDIX ...
40 06-DPP-UM-00147 02/12ENGINEERING UNITS FOR RATE INTERVAL RATE INT -- Time Interval for Flow Rate (Choice) MIN Minutes HOUR Hours DAY
06-DPP-UM-00147 02/12 41FLUID SPECIFIC GRAVITY SP GRAV -- Fluid Specic Gravity (Value) Unitless ValueAllows adjustments to be made to the spec
42 06-DPP-UM-00147 02/12CONFIGURE I/O MODULE 1 CFG MOD1 -- Congure I/O Module 1 (Choice) YES NOThis prompt allows access to the setup parame
06-DPP-UM-00147 02/12 43420MA CALIBRATIONThe 4-20 mA ISO-MOD is factory calibrated and should not require adjustment unless it is replaced.NOTE: Th
44 06-DPP-UM-00147 02/12420TEST 420 MA OUTPUT TESTAllows a simulated value to be output from the 4-20 mA output. By incriminating this value, th
06-DPP-UM-00147 02/12 45ISOMOD DUAL RELAY CONFIGURATIONDUAL RELAYRELAY 1 AND RELAY 2NONETOTALFLOWOFF <ON >ERRORSTwo independent SPDT (single-p
46 06-DPP-UM-00147 02/12ERROR ALARM RELAYWhen a relay is set to ERROR mode, the relay will activate when any error occurs in the ow meter that has
06-DPP-UM-00147 02/12 47When the unit is powered up, there is a delay before the unit begins transmitting sound into the pipe. During this time, the
48 06-DPP-UM-00147 02/12GAIN CONTROLGAIN POT DIGITAL GAIN POT 0-64Using the arrow keys, increase or decrease the numerical value to set the sign
06-DPP-UM-00147 02/12 49LINEARIZATIONLINEAR ENTRY OF LINEARIZATION DATAThe Linearization feature allows for correction of ow readings caused by n
06-DPP-UM-00147 02/12 5FIGURESFIGURE 1.1 TRANSDUCER LOCATIONS ...
50 06-DPP-UM-00147 02/12PART 5 STARTUP AND TROUBLESHOOTINGDFX STARTUP REQUIREMENTSNOTE: The DFX ow meter system requires a full pipe of owing l
06-DPP-UM-00147 02/12 51TROUBLESHOOTINGSymptom ResolutionDisplay does not light up1. Insucient power to DFX monitor – measure voltage at J22. Power
52 06-DPP-UM-00147 02/12Symptom ResolutionRate Pulse output does not match data collection system1. Verify 0 Hz and MAX Hz ow settings2. Place osci
06-DPP-UM-00147 02/12 53APPENDIXSPECIFICATIONSSYSTEMMeasuring PrincipleDoppler Ultrasonic.Velocity Range0.15 to 30 FPS (0.05 to 9 MPS); minimum cali
54 06-DPP-UM-00147 02/12TRANSDUCERSTypeCompression mode Ultrasonic; 625 kHz.Housing MaterialsStandard Clamp-on NEMA 6* (IP 67) -40 °F to +250 °F (
06-DPP-UM-00147 02/12 55MENU MAPSNUMERIC ENTRYPIPE ID Pipe Inside DiameterSECMINHOURDAYRATE INT Rate IntervalX PT 01(÷100)X PT 1 (÷10) X 1 (X1)X 10
56 06-DPP-UM-00147 02/12NONE4-20 MARATERELAYMOD TYPE Module TypeNumeric EntryFLOW 4MA 4 mA Flow ValueNumeric EntryFLOW 20MA 20 mA Flow ValueYESNO
06-DPP-UM-00147 02/12 57TABLE A 3.1 STEEL, STAINLESS STEEL, P.V.C. PIPESTANDARD CLASSESNominal Pipe Size InchesOutside DiameterSCH 5SCH 10(Lt Wal
58 06-DPP-UM-00147 02/12TABLE A 3.1 - STEEL, STAINLESS STEEL, P.V.C. PIPESTANDARD CLASSESNominal Pipe Size InchesOutside DiameterSCH 60 X STG. SCH
06-DPP-UM-00147 02/12 59TABLE A 3.2 TUBE DATANominal DiameterCOPPER TUBINGCopper & Brass PipeALUMINUMNominal DiameterCOPPER TUBINGCopper &
6 06-DPP-UM-00147 02/12TABLESTABLE 2.1 STRAPS REQUIRED VS. PIPE SIZE ...
60 06-DPP-UM-00147 02/12TABLE A 3.3 DUCTILE IRON PIPE STANDARD CLASSESSize(Inches)ClassMortarLiningSize(Inches)ClassMortarLining50 51 52 53 54
06-DPP-UM-00147 02/12 61TABLE A 3.4 CAST IRON PIPE STANDARD CLASSESSize(Inches)ClassSize(Inches)ClassABCDEFGH ABCDEFGH3”O.D. 3.80 3.96 3.96 3.9
62 06-DPP-UM-00147 02/12LIMITED WARRANTY AND DISCLAIMERDYNASONICS, division of Racine Federated Inc. warrants to the end purchaser, for a period of
06-DPP-UM-00147 02/12 63WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT WEEE DIRECTIVEIn the European Union, this label indicates that this product shou
64 06-DPP-UM-00147 02/12RETURN/SALES INFORMATION CONTACTS AND PROCEDURESCUSTOMER SERVICE/APPLICATION ENGINEER:If you have a question regarding order
Division of Racine Federated Inc.8635 Washington AvenueRacine, WI 53406-3738Toll-Free in U.S. and CanadaTel: 800-535-3569 Fax: 800-732-8354Tel:
06-DPP-UM-00147 02/12 7QUICKSTART OPERATING INSTRUCTIONSThis manual contains detailed operating instructions for all aspects of the DFX ow instrume
8 06-DPP-UM-00147 02/12FLOWTop Viewof PipeFIGURE 1.2 TRANSDUCER DIRECTION3 TRANSDUCER CONNECTIONS1) Mount DFX monitor within the length of the t
06-DPP-UM-00147 02/12 9PART 1 INTRODUCTIONGENERALThe DFX ultrasonic ow meter is designed to measure volumetric ow of solids-bearing or aerated l