Network Settings
IP address, IP subnet, IP gateway, and Device Description are
configured through the web interface. IP address and subnet
defaults to 192.168.0.100 and 255.255.255.0. Connection
to the web interface requires an Ethernet crossover cable,
power to the flow meter, and a PC with a web browser.
Typing http://192.168.0.100 in the address bar will allow
connection to the flow meter’s web interface for editing.
Access to the flow meter’s data requires the entry of a
username and password. The flow meter’s default username
is admin and the password is blank from the factory.
OTE:N Changing the IP address will require use of the
new number when trying to access the web page.
Each meter must be setup with a unique IP address
when trying to network multiple units. Important!
When changes are made to the IP address, the
new number must be retained by the user for
future access.
Figure 57: Network login screen
Main Page
The Main Page refreshes itself every 5 seconds and provides real time data from the meter.
AIN PAGE
Enter location information here
Device Values
Signal Strength 22.8
Flow Rate 100.4
Net Totalizer 1659.1
Positive Totalizer 1659.1
Negative Totalizer 0.0
Temp 1 26.5
Temp 2 48.7
This page will automatically refresh every 5 seconds
R eset Totalize rs
Configuration
COMMUNICATIONS PROTOCOLS
Page 75 March 2014