Dynasonics TFXL Clamp-On Ultrasonic Flow Manuel d'utilisateur Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 44
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
06-TTM-UM-00158 8/2012 9
Wiring methods and practices are to be made in accordance
with the NEC - National Electrical Code® - and/or other local
ordinances that may be in e ect. Consult the local electrical
inspector for information regarding wiring regulations.
When making connections to the  eld wiring terminals
inside the  ow meter, strip back the wire insulation approxi-
mately 0.25 inch (6 mm). Stripping back too little may cause
the terminals to clamp on the insulation and not make good
contact. Stripping back too much insulation may lead to a
situation where the wires could short together between ad-
jacent terminals. Wires should be secured in the  eld wiring
terminals using a screw torque of between 0.5 and 0.6 Nm.
If the DC ground terminal is to be utilized as a protec-
tive conductor terminal, the protective conductor shall be
applied  rst and secured independently of other connec-
tions. The protective conductor shall be connected in
such a way that it is unlikely to be removed by servicing
not involving the protective conductor or there shall be a
warning marking requiring the replacement of the protective
conductor after removal.
Power the TFXL  ow meter with a Class 2 direct current
(DC) power source. The power source should be capable of
supplying between 11 and 28 VDC at a minimum of 250 milli-
amps. With the power from the DC power source disabled or
disconnected, connect the positive supply wire and ground
to the appropriate  eld wiring terminals in the  ow meter.
See Figure 1.5. A wiring diagram decal is located on the inner
cover of the  ow meter enclosure for reference.
IMPORTANT NOTE:
Not following instructions properly may impair
safety of equipment and/or personnel.
IMPORTANT NOTE:
Must be operated by a power supply suitable for
the location.
IMPORTANT NOTE:
Do not connect or disconnect either power
or outputs unless the area is known to be
nonhazardous
IMPORTANT NOTE:
Do not connect the interface cable between a
TFXL  ow meter and a personal computer unless
the area is known to be non-hazardous.
TRANSDUCER CONNECTIONS
FIGURE 1.3  TRANSDUCER CONNECTIONS
To access terminal strips for wiring,  rst loosen the four
screws holding the top of the case to the bottom.
NOTE: The four screws are “captive” screws and cannot be
removed from the top of the case.
If the unit has a display remove the four Phillips head screws
that hold the display to the main circuit board and carefully
move it out of the way. Do not over stress the ribbon cable
located between the display and the microprocessor circuit
boards.
Guide the transducer terminations through the transmitter
conduit hole located in the bottom-left of the enclosure.
Secure the transducer cable with the supplied conduit nut (if
exible conduit was ordered with the transducer).
NOTE: TFXL models with integral transducers have the trans-
ducers connected at the factory and the transducer connections
section can be skipped.
The terminals within TFXL are of a screw-down barrier
terminal type. Depending on the type of transducers being
used there are two terminal strip arrangements possible.
Remote mount small pipe transducers are connected to the
terminals found on the main circuit board.
Remote mount transducers are connected to a daughter
board found on the left hand side of the meter.
Connect the appropriate wires at the corresponding screw
terminals in the transmitter. Observe upstream and down-
stream orientation and wire polarity. See Figure 1.3.
NOTE: High temperature transducer cables come with red and
black wire colors. For the red and black combination, the red
wire is positive (+) and the black wire is negative (-).
Vue de la page 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 43 44

Commentaires sur ces manuels

Pas de commentaire