Dynasonics TFX Ultra Transit Time Flow Meters Manuel d'utilisateur Page 78

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 108
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 77
Protocol Implementation Conformance Statement (Normative)
BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT
Date: 03/22/2011
Vendor Name: Racine Federated Inc
Product Name: TFX Ultra Flow meter
Product Model Number: TFX
Application Software Version: 1.08 Firmware Revision: N/A BACnet Protocol Revision: 4
Product Description: Clamp-on ultrasonic flow and energy meters for liquids
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):
y Data Sharing-ReadProperty-B (DS-RP-B)
y Data Sharing-WriteProperty-B (DS-WP-B)
y Data Sharing - ReadProperty Multiple - B (DS-RPM-B)
y Data Sharing - WriteProperty Multiple - B (DS-WPM-B)
y Device Management-Dynamic Device Binding-B (DM-DDB-B)
y Device Management-Dynamic Object Binding-B (DM-DOB-B)
y Device Management-DeviceCommunicationControl-B (DM-DCC-B)
Segmentation Capability:
Segmented requests supported Window Size
Segmented responses supported Window Size
Standard Object Types Supported:
y Device Object
y Analog Input Object
y Binary Output Object
BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT
Page 78 March 2014