Rev. 5/09 - 2.10 - TFXP
2. Place the upstream transducer in position and secure with a
mounting strap. Straps should be placed in the arched groove
on the end of the transducer. A screw is provided to help hold
the transducer onto the strap. Verify that the transducer is true
to the pipe — adjust as necessary. Tighten the transducer strap
securely.
3. Place the downstream transducer on the pipe at the calculated
transducer spacing. See Figure 2.5. Using firm hand pressure,
slowly move the transducer both towards and away from the
upstream transducer while observing signal strength. Signal
strength can be displayed on the TFX display or on the main
data screen in ULTRALINK. See Part 4 of this manual for
details regarding the ULTRALINK software utility. Clamp the
transducer at the position where the highest signal strength is
observed. The factory default signal strength setting is 5
percent, however there are many application specific conditions
that may prevent the signal strength from attaining this level. If
after trying alternate transducer locations and/or mounting
modes the signal strength remains below 5 percent, then
reducing the Low Signal Cutoff setting may be necessary. A
minimum signal strength of 2 percent is acceptable as long as
the 2 percent signal is maintained under all conditions.
(Top view of pipe)
Figure 2.5 — Transducer Positioning
Transducer
Positioning
PART 2 - TRANSDUCER & RTD INSTALLATION